Advanced SNMP
Load MIBs, explore a device, define states per value, per-port thresholds and SNMP tables.
Load MIBs
Settings > Monitoring > MIB > Load MIBs: drop your vendors’ MIB files, several at once. A module that imports another one waits until that one is loaded; the list says so. OIDs are then named everywhere: explorer, checks, received traps ("upsOnBattery upsState.0=onBattery(2)" instead of a string of digits).
Standard MIBs
No MIB is embedded: also load the standard MIBs you need (SNMPv2-MIB, IF-MIB, HOST-RESOURCES-MIB…).
Explore a device
Item’s page > Monitoring > SNMP explorer: reads a branch of the device (system, interfaces, storage, hardware, vendor branch…) with the monitoring credential or another one. Copy the OID to turn it into a check in a profile.
States per value
In an SNMP profile, a check can have states per value instead of thresholds: Take the values from the MIB fills the enumeration (ifOperStatus: up, down…) and suggests a state for each one, to review.
Per-port thresholds
An SNMP profile with interfaces accepts usage thresholds (% of speed, in the busiest direction) and errors per second, applied to every active and connected port; the message names the port ("Gi0/2: 95.0 % in"). To alert on some ports only, tick Watched in the item’s Interfaces tab.
SNMP tables
One series per row of a table, like PRTG’s "SNMP Custom Table" sensors: tick Column of an SNMP table on a check, set
the OID of the column (without row number, for example 1.3.6.1.2.1.25.2.3.1.6 hrStorageUsed) and, optionally, the
OID of the column that names the rows (1.3.6.1.2.1.25.2.3.1.3 hrStorageDescr).
Each row becomes a series (disk.used{row=/var}…) with the check’s thresholds, and the alert names the faulty row.
Examples: batteries or phases of a UPS, temperature probes of a chassis, IP SLA operations of a Cisco router
(rttMonLatestRttOperCompletionTime). 256 rows at most per check.